VIOX VM2-125 1-4P MCB

VIOX VM2-125 MCB offers robust protection for electrical systems up to 125A. This IEC/EN 60898-1 compliant device features a 10kA short-circuit capacity and supports current ratings from 20A to 125A at 230/400V AC. Available in 1P, 1P+N, 2P, 3P, 3P+N, and 4P configurations, it provides C and D tripping curves for versatile applications. Key advantages include a 6kV impulse withstand voltage, contact position indication, and dual protection mechanisms for overload and short-circuit protection. With up to 10,000 cycle electro-mechanical endurance, this MCB ensures reliable protection for industrial, commercial, and residential installations. Its flexible connection capacity up to 50mm², 20mm terminal height, and easy DIN rail mounting make it ideal for various circuit protection needs. The device operates effectively at 50/60Hz and offers comprehensive overload current protection characteristics, making it suitable for non-frequent switching operations in diverse building applications.

Send your requirements, we will quote for you within 12 hours​

VIOX VM2-125 1-4P Miniature Circuit Breaker (MCB)

Overview

The VIOX VM2-125 Miniature Circuit Breaker (MCB) is designed for protection against overload and short circuits in AC 50Hz/60Hz systems with rated voltage 230V/400V and rated current from 20A to 125A. It’s suitable for non-frequent on-and-off switch operations under normal circumstances and is widely used in industrial, commercial, high-rise buildings, and household applications.

Key Features

  • High short-circuit capacity of 10kA
  • Protects circuits carrying currents up to 125A
  • Contact position indication
  • Suitable as main switch in household and similar installations
  • Excellent price-quality ratio

Technical Specifications

  • Standard: IEC/EN 60898-1
  • Pole configurations: 1P, 1P+N, 2P, 3P, 3P+N, 4P
  • Rated voltage: AC 230V/400V
  • Rated current: 20A, 25A, 32A, 40A, 50A, 63A, 80A, 100A, 125A
  • Tripping curve: C, D
  • Rated short-circuit capacity (Icn): 10000A
  • Rated service short-circuit capacity (Ics): 7500A
  • Rated frequency: 50/60Hz
  • Rated impulse withstand voltage (Uimp): 6kV
  • Connection terminal: Pillar terminal with clamp

Performance Characteristics

  • Electro-mechanical endurance: In≤100A = 10000 cycles, In=125A = 8000 cycles
  • Terminal connection height: 20mm
  • Connection capacity: Flexible conductor 35mm², Rigid conductor 50mm²
  • Installation: On symmetrical DIN rail 35mm or panel mounting

Overload Current Protection Characteristics

Test Tripping Type Test Current Initial State Tripping Time or Non-tripping Time Provision Result
a Time-delay 1.05In Cold t≤1h (In≤63A), t≤2h (In>63A) No Tripping
b Time-delay 1.30In After test a t<1h (In≤63A), t<2h (In>63A) Tripping
c Time-delay 2In Cold 1s<t<60s (In≤63A), 1s<t<120s (In>63A) Tripping
d Instantaneous 8In Cold t≤0.2s No Tripping
e Instantaneous 12In Cold t<0.2s Tripping

Applications

  • Industrial electrical systems
  • Commercial buildings
  • High-rise buildings
  • Household electrical installations

Working Principle

The VIOX VM2-125 MCB operates using a bimetallic strip for overload protection and an electromagnetic mechanism for short-circuit protection. During an overload, the bimetallic strip heats and bends, releasing an electromechanical latch connected to the operating mechanism. This action opens the MCB contacts, interrupting the current flow. For short circuits, the electromagnetic mechanism provides rapid tripping. Manual reset is required to restore current flow after a trip.