VIOX VSP1-C40/2(S) Instickbar enpolig SPD
VIOX VSP1-C40/2(S) Pluggable Single-Pole SPD offers robust surge protection for sub-distribution boards. This Class II/Type 2/Type 1CA device safeguards L-PE and N-PE modes with 20kA nominal and 40kA maximum discharge current. Featuring high-energy MOV elements, it operates from 60V to 400V AC with < 25ns response time. The pluggable design ensures easy installation on 35mm DIN rails. IEC 61643-11:2011 and EN 61643-11:2012 compliant, it provides voltage protection levels from 0.4kV to 2kV. With IP20 protection, thermal safeguards, and optional remote contacts, this versatile SPD suits various electrical installations, combining reliability and performance in a compact, user-friendly package for enhanced power system protection in demanding applications.
Skicka dina krav, vi kommer att offerera för dig inom 12 timmar
- TEL:+8618066396588
- Whatsapp:+8618066396588
- Email:sales@viox.com
VIOX VSP1-C40/2(S) Instickbar enpolig SPD
Översikt
The VIOX VSP1-C40/2(S) is a high-performance Pluggable Single-Pole Surge Protective Device (SPD) designed for use in sub-distribution boards. This versatile device offers robust protection for L-PE and N-PE modes, making it an ideal solution for various electrical installations.
Viktiga funktioner
- Klass II, typ 2, typ 1CA-enhet
- Plats för användning: Underdistributionscentraler
- Skyddsläge: L-PE, N-PE
- Klassning för överspänning: In = 20 kA (8/20 μs)
- IEC/EN/UL Kategori: Klass II / Typ 2 / Typ 1CA
- Skyddande element: Högenergi MOV
- Hölje: Pluggbar design
- Överensstämmelse: IEC 61643-11:2011, EN 61643-11:2012
Tekniska specifikationer
IEC Elektrisk | 75 | 150 | 275 | 320 | 385 | 440 |
---|---|---|---|---|---|---|
Nominell AC-spänning (50/60Hz) | 60 V | 120 V | 230 V | 230 V | 230 V | 400 V |
Maximal kontinuerlig driftspänning (AC) | 75 V | 150 V | 275V | 320 V | 385 V | 440 V |
Nominell urladdningsström (8/20 μs) | 20 kA | 20 kA | 20 kA | 20 kA | 20 kA | 20 kA |
Maximal urladdningsström (8/20 μs) | 40 kA | 40 kA | 40 kA | 40 kA | 40 kA | 40 kA |
Skyddsnivå för spänning | 0.4 kV | 1 kV | 1,5 kV | 1.6 kV | 1,8 kV | 2 kV |
Impulsström (10/350 μs) Iimp (L-N) | 7 kA | |||||
Svarstid | < 25 ns | |||||
Reservsäkring (max) | 125 A gL / gG | |||||
Nominell kortslutningsström (AC) | 25 kA / 50 kA | |||||
TOV Motstånd 5s | 90V | 180V | 335V | 335V | 335V | 580V |
TOV 120min | 115V | 230V | 440V | 440V | 440V | 765V |
läge | Motstånd | Motstånd | Säkert fel | Säkert fel | Säkert fel | Säkert fel |
Mekaniska och miljömässiga specifikationer
- Driftstemperaturområde: -40°F till +158°F [-40°C till +70°C].
- Tillåten luftfuktighet vid drift: 5%...95%
- Atmosfäriskt tryck och höjd: 80k Pa ... 106k Pa / -500 m....2000 m
- Vridmoment för terminalskruv: 39,9 lbf.in [4,5 Nm]
- Ledarens tvärsnitt (max): 2 AWG (solid, fåtrådig) / 4 AWG (flexibel)
- 35 mm² (solid, fåtrådig) / 25 mm² (flexibel)
- Montering: 35 mm DIN-skena, EN 60715
- Grad av skydd: IP 20 (inbyggd)
- Material i höljet: Termoplast: Släckningsgrad UL 94 V-0
- Termiskt skydd: Ja
- Drifttillstånd / felindikering: Grön ok / Röd defekt
Ytterligare funktioner
- Fjärrkontakter (RC): Tillval
- RC Omkopplingskapacitet: AC: 250V / 0,5 A; DC: 250V / 0,1 A;125V / 0,2 A;75V / 0,5 A
- RC-ledarens tvärsnitt (max): 16 AWG (Solid) / 1,5 mm² (Solid)