VIOX VSP1-C40/2(S) Priključni enopolni SPD
VIOX VSP1-C40/2(S) Pluggable Single-Pole SPD offers robust surge protection for sub-distribution boards. This Class II/Type 2/Type 1CA device safeguards L-PE and N-PE modes with 20kA nominal and 40kA maximum discharge current. Featuring high-energy MOV elements, it operates from 60V to 400V AC with < 25ns response time. The pluggable design ensures easy installation on 35mm DIN rails. IEC 61643-11:2011 and EN 61643-11:2012 compliant, it provides voltage protection levels from 0.4kV to 2kV. With IP20 protection, thermal safeguards, and optional remote contacts, this versatile SPD suits various electrical installations, combining reliability and performance in a compact, user-friendly package for enhanced power system protection in demanding applications.
Pošljite svoje zahteve, ponudbo vam bomo posredovali v 12 urah
- TEL:+8618066396588
- Whatsapp:+8618066396588
- Email:sales@viox.com
VIOX VSP1-C40/2(S) Priključni enopolni SPD
Pregled
The VIOX VSP1-C40/2(S) is a high-performance Pluggable Single-Pole Surge Protective Device (SPD) designed for use in sub-distribution boards. This versatile device offers robust protection for L-PE and N-PE modes, making it an ideal solution for various electrical installations.
Ključne lastnosti
- Class II, Type 2, Type 1CA device
- Lokacija uporabe: Sub-distribucijske plošče
- Mode of Protection: L-PE, N-PE
- Ocene prenapetosti: In = 20 kA (8/20 μs)
- IEC/EN/UL Category: Class II / Type 2 / Type 1CA
- Zaščitni elementi: Visokoenergijski MOV
- Stanovanja: Priključna zasnova
- Compliance: IEC 61643-11:2011, EN 61643-11:2012
Tehnične specifikacije
IEC Electrical | 75 | 150 | 275 | 320 | 385 | 440 |
---|---|---|---|---|---|---|
Nominal AC Voltage (50/60Hz) | 60 V | 120 V | 230 V | 230 V | 230 V | 400 V |
Maximum Continuous Operating Voltage (AC) | 75 V | 150 V | 275V | 320 V | 385 V | 440 V |
Nazivni tok praznjenja (8/20 μs) | 20 kA | 20 kA | 20 kA | 20 kA | 20 kA | 20 kA |
Največji tok praznjenja (8/20 μs) | 40 kA | 40 kA | 40 kA | 40 kA | 40 kA | 40 kA |
Raven zaščite pred napetostjo | 0.4 kV | 1 kV | 1.5 kV | 1.6 kV | 1.8 kV | 2 kV |
Impulse Current (10/350μs) Iimp (L-N) | 7kA | |||||
Odzivni čas | < 25 ns | |||||
Varnostna varovalka (največ) | 125 A gL / gG | |||||
Nazivni tok kratkega stika (AC) | 25 kA / 50 kA | |||||
TOV Withstand 5s | 90V | 180V | 335V | 335V | 335V | 580V |
TOV 120min | 115V | 230V | 440V | 440V | 440V | 765V |
mode | Withstand | Withstand | Safe Fail | Safe Fail | Safe Fail | Safe Fail |
Mehanske in okoljske specifikacije
- Območje delovne temperature: -40 °F do +158 °F [-40°C do +70°C]
- Dovoljena delovna vlažnost: 5%...95%
- Atmosferski tlak in nadmorska višina: 80k Pa ... 106k Pa / -500 m....2000 m
- Navorni moment vijaka za priključek: 39,9 lbf.in [4,5 Nm]
- Prečni prerez vodnika (max): 2 AWG (polni, pleteni) / 4 AWG (upogljivi)
- 35 mm² (polni, pleteni) / 25 mm² (upogljivi)
- Montaža: EN 60715
- Stopnja zaščite: IP 20 (vgrajeno)
- Material ohišja: Stopenj gašenja UL 94 V-0
- Toplotna zaščita: Da:
- Delovno stanje / indikacija napake: Zelena v redu / rdeča napaka
Dodatne funkcije
- Daljinski stiki (RC): Izbirni
- RC Preklopna zmogljivost: AC: 250 V / 0,5 A; DC: 250 V / 0,1 A; 125 V / 0,2 A; 75 V / 0,5 A
- Prečni prerez vodnika RC (max): 16 AWG (polni) / 1,5 mm² (polni)