VIOX VM2-125 1-4P MCB
VIOX VM2-125 MCB offers robust protection for electrical systems up to 125A. This IEC/EN 60898-1 compliant device features a 10kA short-circuit capacity and supports current ratings from 20A to 125A at 230/400V AC. Available in 1P, 1P+N, 2P, 3P, 3P+N, and 4P configurations, it provides C and D tripping curves for versatile applications. Key advantages include a 6kV impulse withstand voltage, contact position indication, and dual protection mechanisms for overload and short-circuit protection. With up to 10,000 cycle electro-mechanical endurance, this MCB ensures reliable protection for industrial, commercial, and residential installations. Its flexible connection capacity up to 50mm², 20mm terminal height, and easy DIN rail mounting make it ideal for various circuit protection needs. The device operates effectively at 50/60Hz and offers comprehensive overload current protection characteristics, making it suitable for non-frequent switching operations in diverse building applications.
Trimiteți cerințele dvs., vom cita pentru dvs. în termen de 12 ore
- TEL:+8618066396588
- Whatsapp:+8618066396588
- Email:sales@viox.com
VIOX VM2-125 1-4P Miniature Circuit Breaker (MCB)
Prezentare generală
The VIOX VM2-125 Miniature Circuit Breaker (MCB) is designed for protection against overload and short circuits in AC 50Hz/60Hz systems with rated voltage 230V/400V and rated current from 20A to 125A. It’s suitable for non-frequent on-and-off switch operations under normal circumstances and is widely used in industrial, commercial, high-rise buildings, and household applications.
Caracteristici principale
- High short-circuit capacity of 10kA
- Protects circuits carrying currents up to 125A
- Contact position indication
- Potrivit ca întrerupător principal în instalații casnice și similare
- Excellent price-quality ratio
Specificații tehnice
- Standard: IEC/EN 60898-1
- Configurația polilor: 1P, 1P+N, 2P, 3P, 3P+N, 4P
- Tensiune nominală: AC 230V/400V
- Rated current: 20A, 25A, 32A, 40A, 50A, 63A, 80A, 100A, 125A
- Tripping curve: C, D
- Rated short-circuit capacity (Icn): 10000A
- Rated service short-circuit capacity (Ics): 7500A
- Frecvență nominală: 50/60Hz
- Tensiunea nominală de rezistență la impulsuri (Uimp): 6kV
- Terminal de conectare: Terminal pilon cu clemă
Caracteristici de performanță
- Electro-mechanical endurance: In≤100A = 10000 cycles, In=125A = 8000 cycles
- Terminal connection height: 20mm
- Capacitate de conectare: Conductor flexibil 35mm², Conductor rigid 50mm²
- Instalare: Pe șină DIN simetrică de 35 mm sau montare pe panou
Caracteristici de protecție la curent de suprasarcină
Test | Tip de declanșare | Curent de testare | Starea inițială | Dispoziția privind timpul de declanșare sau timpul de ne declanșare | Rezultat |
---|---|---|---|---|---|
a | Întârziere | 1.05In | Rece | t≤1h (In≤63A), t≤2h (In>63A) | Fără împiedicare |
b | Întârziere | 1.30In | După testul a | t<1h (In≤63A), t<2h (In>63A) | Tripping |
c | Întârziere | 2In | Rece | 1s<t<60s (In≤63A), 1s<t<120s (In>63A) | Tripping |
d | Instantaneous | 8In | Rece | t≤0.2s | Fără împiedicare |
e | Instantaneous | 12In | Rece | t<0.2s | Tripping |
Aplicații
- Industrial electrical systems
- Clădiri comerciale
- Clădiri înalte
- Household electrical installations
Principiul de funcționare
The VIOX VM2-125 MCB operates using a bimetallic strip for overload protection and an electromagnetic mechanism for short-circuit protection. During an overload, the bimetallic strip heats and bends, releasing an electromechanical latch connected to the operating mechanism. This action opens the MCB contacts, interrupting the current flow. For short circuits, the electromagnetic mechanism provides rapid tripping. Manual reset is required to restore current flow after a trip.