VIOX VL16-40 AC Tip 1P+N RCBO
VIOX VL16-40 AC Type 1P+N RCBO offers comprehensive protection for household and commercial distribution systems. This IEC/EN61009-1 compliant device safeguards against earth faults, short-circuits, and overloads with a 10kA rated short-circuit capacity. Available in 1A to 40A ratings, it operates at 240V AC, 50/60Hz, with residual current options of 30mA, 100mA, or 300mA. Featuring B, C, or D tripping curves and instantaneous tripping ≤0.1s, it provides efficient protection against insulation failures and direct human contact. With easy DIN rail mounting and 4000 cycle electro-mechanical endurance, this versatile RCBO ensures reliable electrical safety for various applications.
Trimiteți cerințele dvs., vom cita pentru dvs. în termen de 12 ore
- TEL:+8618066396588
- Whatsapp:+8618066396588
- Email:sales@viox.com
VIOX VL16-40 AC Type 1P+N Residual Current Circuit Breaker with Overcurrent Protection RCBO
Prezentare generală
The VIOX VL16-40 RCBO provides comprehensive protection for household and commercial distribution systems. It offers protection against earth fault/leakage current, short-circuit, overload, and functions as an isolation device. This device effectively safeguards electric equipment against insulating failure and provides complementary protection against direct contact by human body.
Caracteristici principale
- Standarde: IEC/EN61009-1
- Type: Electro-magnetic type
- Residual current characteristics: AC A
- Polul nr.: 1P+N
- Curbă de declanșare: B, C, D
- Rated short-circuit capacity: 10kA
- Rated current (A): 1A, 2A, 3A, 4A, 6A, 10A, 16A, 20A, 25A, 32A, 40A
- Tensiune nominală: 240V AC
- Frecvență nominală: 50/60Hz
- Curent de funcționare rezidual nominal (mA): 0,03, 0,1, 0,3
- Tripping duration: instantaneous≤0.1s
- Rezistență electro-mecanică: 4000 de cicluri
Specificații tehnice
- Connection terminal: pillar terminal with clamp
- Connection capacity: Rigid conductor 16mm²
- Terminal connection height: 21.5mm
- Installation: On symmetrical DIN rail 35mm or Panel mounting
Caracteristici de protecție la curent de suprasarcină
Procedura de testare | Tip | Curent de testare | Starea inițială | Limita de timp pentru declanșare sau ne declanșare | Rezultat așteptat | Observație |
---|---|---|---|---|---|---|
a | B,C,D | 1.13In | rece | t≥1h | No tripping | |
b | 1.45In | după testul a | t<1h | împiedicare | Current in the 5s in the increase of stability | |
c | 2.55In | rece | 1s<t<60s | împiedicare | ||
d | B C D |
3In 5In 10In |
rece | t≥0.1s | No tripping | Porniți comutatorul auxiliar pentru a închide curentul |
e | B C D |
5In 10In 20In |
rece | t<0,1s | împiedicare | Porniți comutatorul auxiliar pentru a închide curentul |
The terminology “cold state” refers to that no load is carried before testing at the reference setting temperature.
Residual Current Action Breaking Time
Tip | În/A | I△n/A | Curentul rezidual (I△) corespunde următorului timp de rupere (S) | ||||
AC type | any value | any value | În | 2In | 5In | 5A,10A,20A,50A,100A,200A,500A | |
A type | any value | >0.01 | 1.4In | 2.8In | 7In | ||
0.3 | 0.15 | 0.04 | 0.04 | Timp maxim de pauză | |||
RCBO de tip general al cărui curent IΔn este de 0,03mA sau mai mic poate utiliza 0,25A în loc de 5IΔn. |