VIOX VRC3-63 2P 25A RCCB

VIOX VRC3-63 RCCB offers superior protection against earth faults and leakage currents for systems up to 25A. This IEC61008-compliant device features a 10kA rated conditional short-circuit current and supports residual operating currents of 0.03A, 0.1A, 0.3A, and 0.5A. Available in 2P configuration, it operates at 230/400V AC, 50/60Hz. Key advantages include both electronic and electro-magnetic types, IP20 protection, and a 4,000-cycle electro-mechanical endurance. With its clear position indication, finger-protected terminals, and fire-resistant construction, this RCCB ensures easy operation and enhanced safety. Suitable for residential, commercial, and industrial applications, it offers automatic circuit disconnection and high short-circuit tolerance. The device’s 25mm² terminal capacity, 2.0Nm fastening torque, and 35.5mm DIN rail mounting make it ideal for various earth leakage protection needs in distribution boards and electrical circuits.

Trimiteți cerințele dvs., vom cita pentru dvs. în termen de 12 ore

VIOX VRC3-63 2P 25A RCCB Electronic/Electro-Magnetic Type Residual Current Circuit Breaker

Prezentare generală

The VIOX VRC3-63 is a versatile Residual Current Circuit Breaker (RCCB) designed to provide superior protection against earth faults and leakage currents. Available in both electronic and electro-magnetic types, this RCCB offers reliable performance and enhanced safety features for various electrical installations.

Caracteristici principale

  • Protection against earth fault/leakage current with isolation function
  • High short-circuit current withstand capacity
  • Clear contact position indication
  • Finger-protected connection terminals for added safety
  • Fire-resistant plastic parts for durability against abnormal heating and strong impacts
  • Automatic circuit disconnection when earth fault/leakage current exceeds rated sensitivity
  • Independent operation from power supply and line voltage
  • Resistant to external interference and voltage fluctuations

Specificații tehnice

  • Standard: IEC61008
  • Mode: Electro-magnetic type, electronic type
  • Residual current characteristics: A, AC
  • Pole configuration: 2P (4P also available)
  • Rated making and breaking capacity: 500A (In=25A, 40A) or 10InA (In=63A, 80A, 100A, 125A)
  • Rated current: 25A (40A, 63A also available)
  • Rated voltage: AC 230(240)/400(415)V
  • Frecvență nominală: 50/60Hz
  • Rated residual operating current (I△n): 0.03A, 0.1A, 0.3A, 0.5A
  • Curent rezidual nominal de nefuncționare: 0,5I△n
  • Rated conditional short-circuit current (Inc): 10kA
  • Rated conditional residual short-circuit current (I△c): 10kA
  • Tripping duration: instantaneous tripping ≤0.3s (0.1s)
  • Residual tripping current range: 0.5I△n~I△n
  • Rezistență electro-mecanică: 4000 de cicluri
  • Connection capacity: Rigid conductor 25mm²
  • Terminal connection height: 21mm
  • Terminal de conectare: Terminal pilon cu clemă
  • Fastening torque: 2.0Nm
  • Installation: On symmetrical DIN rail 35.5mm or panel mounting
  • Protection class: IP20

Residual Current Action Breaking Time

Tip In (A) I△n (A) Residual Current (I△) Corresponding Breaking Time (s) Notă
I△n 2 I△n 5 I△n 5A,10A,20A,50A,100A,200A,500A
Tip general Orice valoare Orice valoare 0.3 0.15 0.04 0.04 Timp maxim de pauză
S Type ≥25 >0.03 0.5 0.2 0.15 0.15 Timp maxim de pauză
0.13 0.06 0.05 0.04 Min non-driving time

Note: The general type RCBO whose current IΔn is 0.03mA or less can use 0.25A instead of 5IΔn.

Aplicații

  • Sisteme electrice rezidențiale
  • Clădiri comerciale
  • Instalații industriale
  • Tablouri de distribuție
  • Protecția împotriva scurgerilor la pământ în diferite circuite electrice

Avantaje

  • Dual protection: earth fault and leakage current
  • High short-circuit current tolerance for improved reliability
  • Easy installation with DIN rail or panel mounting options
  • Indicație clară a stării pentru identificarea rapidă a defecțiunilor
  • Durable construction with fire-resistant materials
  • În conformitate cu standardele internaționale pentru asigurarea calității

Caracteristici de siguranță

  • Protecție împotriva defecțiunilor la pământ
  • Leakage current protection
  • Isolation function
  • Finger-protected connection terminals
  • Automatic circuit disconnection for faults exceeding rated sensitivity

Dimensiune

Asigurarea calității

VIOX se angajează să furnizeze RCCB de înaltă calitate care îndeplinesc standardele internaționale. Produsele noastre sunt supuse unor teste riguroase pentru a asigura fiabilitatea, siguranța și performanța pe termen lung în diverse instalații electrice.

Produse conexe

Cereți o ofertă acum

Cereți o ofertă acum