VIOX VSP1-D20/1(S)+1 Pluggbar enpolet SPD
VIOX VSP1-D20/1(S)+1 Pluggable Single-Pole SPD offers comprehensive surge protection for sub-distribution boards. This Class II+III/Type 2+3 device safeguards L-N and N-PE modes with 10kA nominal and 20kA maximum discharge current. Featuring high-energy MOV and GDT elements, it operates from 60V to 400V AC with <25ns response time for L-N and <100ns for N-PE. IEC 61643-11:2011 and EN 61643-11:2012 compliant, it provides voltage protection levels from 0.2kV to 1.8kV. With IP20 protection, thermal safeguards, and optional remote contacts, this versatile SPD suits various electrical installations, combining reliability and performance for enhanced power system protection in diverse applications.
Send oss dine krav, så gir vi deg et tilbud innen 12 timer
- TEL:+8618066396588
- Whatsapp:+8618066396588
- Email:sales@viox.com
VIOX VSP1-D20/1(S)+1 Pluggbar enpolet SPD
Oversikt
VIOX VSP1-D20/1(S)+1 er en høytytende pluggbar enpolet overspenningsvern (SPD) designet for bruk i underfordelingsskap. Denne allsidige enheten tilbyr robust beskyttelse for LN- og N-PE-moduser, noe som gjør den til en ideell løsning for ulike elektriske installasjoner.
Viktige funksjoner
- Klasse II, klasse III, type 2, type 3-enhet
- Bruksområde: Underdistribusjonstavler
- Beskyttelsesmodus: LN, N-PE
- Overspenningsverdier: In = 10 kA (8/20 μs)
- IEC/EN/UL Kategori: Klasse II+III / Type 2+3
- Beskyttende elementer: Høyenergi MOV og GDT
- Hus: Pluggbar design
- Samsvar: IEC 61643-11:2011, EN 61643-11:2012
Tekniske spesifikasjoner
IEC Elektrisk | 75 | 150 | 275 | 320 | 385 | 440 |
---|---|---|---|---|---|---|
Nominell vekselstrømspenning (50/60 Hz) | 60 V | 120 V | 230 V | 230 V | 230 V | 400 V |
Maksimal kontinuerlig driftsspenning (AC) (LN) | 75 V | 150 V | 275V | 320 V | 385 V | 440 V |
Maksimal kontinuerlig driftsspenning (AC) (N-PE) | 255V | |||||
Nominell utladningsstrøm (8/20 μs) (LN) / (N-PE) | 10 kV / 10 kA | |||||
Maksimal utladningsstrøm (8/20 μs) (LN) / (N-PE) | 20 kA / 20 kA | |||||
Spenningsbeskyttelsesnivå (LN) / (N-PE) | 0,2 kV/1,5 kV | 0,6 kV/1,5 kV | 1,3 kV/1,5 kV | 1,5 kV/1,5 kV | 1,5 kV/1,5 kV | 1,8 kV/1,5 kV |
Følg strømavbruddsklassifisering (N-PE) | 100Arms | |||||
Responstid (LN) / (N-PE) | < 25 ns / < 100 ns | |||||
Reservesikring (maks.) | 125 A gL / gG | |||||
Kortslutningsstrømklassifisering (AC) (LN) | 10 kA | |||||
TOV-motstand 5s (LN) | 90V | 180V | 335V | 335V | 335V | 580V |
Total verdi 120 min (LN) | 115V | 230V | 440V | 440V | 440V | 765V |
modus | Tåler | Tåler | Sikker feil | Sikker feil | Sikker feil | Sikker feil |
TOV-motstand 200 ms (N-PE) | 1200V |
Mekaniske og miljømessige spesifikasjoner
- Driftstemperaturområde: -40 °F til +158 °F [-40 °C til +70 °C].
- Tillatt luftfuktighet ved drift: 5%...95%
- Atmosfærisk trykk og høyde: 80k Pa ... 106k Pa / -500 m....2000 m
- Dreiemoment for terminalskruer: 39,9 lbf.in [4,5 Nm]
- Ledertverrsnitt (maks.): 2 AWG (massiv, fåtrådet) / 4 AWG (fleksibel)
- 35 mm² (massiv, flertrådet) / 25 mm² (fleksibel)
- Montering: 35 mm DIN-skinne, EN 60715
- Grad av beskyttelse: IP 20 (innebygd)
- Materiale i huset: Termoplast: Slukningsgrad UL 94 V-0
- Termisk beskyttelse: Ja
- Driftstilstand / feilindikering: Grønn ok / Rød defekt
Ytterligere funksjoner
- Fjernkontakter (RC): Valgfritt
- RC-bryterkapasitet: AC: 250V / 0,5 A; DC: 250V / 0,1 A; 125 V / 0,2 A; 75 V / 0,5 A
- Tverrsnitt for RC-leder (maks.): 16 AWG (Solid) / 1,5 mm² (Solid)