VIOX VSP1-C40PV/2(S) 600V pluggbar enpolet SPD
VIOX VSP1-C40PV/2(S) 600V Pluggable Single-Pole SPD offers robust surge protection for photovoltaic systems and sub-distribution boards. This Class II/Type 2/Type 1CA device safeguards L-PE and N-PE modes with 20kA nominal and 40kA maximum discharge current. Featuring high-energy MOV elements, it operates at 600V DC with < 25ns response time. The pluggable design ensures easy installation on 35mm DIN rails. IEC 61643-11:2011 and EN 61643-11:2012 compliant, it provides a voltage protection level of 2.2kV. With IP20 protection, thermal safeguards, and optional remote contacts, this versatile SPD suits various electrical installations, combining reliability and performance for enhanced power system protection in demanding photovoltaic applications.
Send oss dine krav, så gir vi deg et tilbud innen 12 timer
- TEL:+8618066396588
- Whatsapp:+8618066396588
- Email:sales@viox.com
VIOX VSP1-C40PV/2(S) 600V pluggbar enpolet SPD
Oversikt
The VIOX VSP1-C40PV/2(S) 600V is a high-performance Pluggable Single-Pole Surge Protective Device (SPD) designed for use in sub-distribution boards. This versatile device offers robust protection for L-PE and N-PE modes, making it an ideal solution for various electrical installations, particularly in photovoltaic systems.
Viktige funksjoner
- Klasse II, type 2, type 1CA-enhet
- Bruksområde: Underdistribusjonstavler
- Beskyttelsesmodus: L-PE, N-PE
- Overspenningsverdier: In = 20 kA (8/20 μs)
- IEC/EN/UL Kategori: Klasse II / Type 2 / Type 1CA
- Beskyttelseselementer: Høyenergi MOV
- Hus: Pluggbar design
- Samsvar: IEC 61643-11:2011, EN 61643-11:2012
Tekniske spesifikasjoner
IEC Elektrisk | 600 |
---|---|
Nominell vekselspenning | 600V |
Maksimal kontinuerlig driftsspenning (DC) | 600V |
Nominell utladningsstrøm (8/20 μs) | 20 kA |
Maksimal utladningsstrøm (8/20 μs) | 40 kA |
Impulsutladningsstrøm (10/350 μs) | 6.25kA |
Spenningsbeskyttelsesnivå | 2.2kV |
Impulsstrøm (10/350 μs) Iimp (L-N) | 7 kA |
Responstid | < 25 ns |
Reservesikring (maks.) | 125 A gL / gG |
Kortslutningsstrøm (AC) | 25 kA / 50 kA |
TOV Tåler 5s | ? |
TOV 120 min | ? |
modus | Withstand, Safe Fail |
Mekaniske og miljømessige spesifikasjoner
- Driftstemperaturområde: -40 °F til +158 °F [-40 °C til +70 °C].
- Tillatt luftfuktighet ved drift: 5%...95%
- Atmosfærisk trykk og høyde: 80k Pa ... 106k Pa / -500 m....2000 m
- Dreiemoment for terminalskruer: 39,9 lbf.in [4,5 Nm]
- Ledertverrsnitt (maks.): 2 AWG (massiv, fåtrådet) / 4 AWG (fleksibel)
- 35 mm² (massiv, flertrådet) / 25 mm² (fleksibel)
- Montering: 35 mm DIN-skinne, EN 60715
- Grad av beskyttelse: IP 20 (innebygd)
- Materiale i huset: Termoplast: Slukningsgrad UL 94 V-0
- Termisk beskyttelse: Ja
- Driftstilstand / feilindikering: Grønn ok / Rød defekt
Ytterligere funksjoner
- Fjernkontakter (RC): Valgfritt
- RC Switching Capacity: VEKSELSTRØM: 250V / 0,5 A; LIKESTRØM: 250V / 0,1 A;125V / 0,2 A;75V / 0,5 A
- Tverrsnitt for RC-leder (maks.): 16 AWG (Solid) / 1,5 mm² (Solid)