VIOX VSP1-D20/3(S) Pluggable Multi-Pole SPD
VIOX VSP1-D20/3(S) Pluggable Multi-Pole SPD offers robust surge protection for sub-distribution boards. This Class II/Type 2 device safeguards L-PE and N-PE modes with 10kA nominal and 20kA maximum discharge current. Featuring high-energy MOV elements, it operates from 120V to 400V AC with < 25ns response time. The pluggable design ensures easy installation on 35mm DIN rails. IEC 61643-11:2011 and EN 61643-11:2012 compliant, it provides voltage protection levels from 0.6kV to 1.8kV. With IP20 protection, thermal safeguards, and optional remote contacts, this versatile SPD suits various electrical installations, combining reliability and performance in a compact, user-friendly package for enhanced multi-pole power system protection.
Send oss dine krav, så gir vi deg et tilbud innen 12 timer
- TEL:+8618066396588
- Whatsapp:+8618066396588
- Email:sales@viox.com
VIOX VSP1-D20/3(S) Pluggable Multi-Pole SPD
Oversikt
The VIOX VSP1-D20/3(S) is a high-performance Pluggable Multi-Pole Surge Protective Device (SPD) designed for use in sub-distribution boards. This versatile device offers robust protection for both L-PE and N-PE modes, making it an ideal solution for various electrical installations.
Viktige funksjoner
- Class II, Class III, Type 2, Type 3 device
- Bruksområde: Underdistribusjonstavler
- Beskyttelsesmodus: L-PE, N-PE
- Surge Ratings: In = 10 kA (8/20 μs)
- IEC/EN/UL Kategori: Klasse II / Type 2 / Type 1CA
- Beskyttelseselementer: Høyenergi MOV
- Hus: Pluggbar design
- Samsvar: IEC 61643-11:2011, EN 61643-11:2012
Tekniske spesifikasjoner
IEC Elektrisk | 150 | 275 | 320 | 385 | 440 |
---|---|---|---|---|---|
Nominell vekselstrømspenning (50/60 Hz) | 120 V | 230 V | 230 V | 230 V | 400 V |
Maksimal kontinuerlig driftsspenning (AC) | 150 V | 275V | 320 V | 385 V | 440 V |
Nominell utladningsstrøm (8/20 μs) | 10 kA | 10 kA | 10 kA | 10 kA | 10 kA |
Maksimal utladningsstrøm (8/20 μs) | 20 kA | 20 kA | 20 kA | 20 kA | 20 kA |
Spenningsbeskyttelsesnivå | 0.6 kV | 1.3 kV | 1,5 kV | 1,5 kV | 1,8 kV |
Responstid | < 25 ns | ||||
Reservesikring (maks.) | 125 A gL / gG | ||||
Kortslutningsstrøm (AC) | 10 kA | ||||
TOV Tåler 5s | 180V | 335V | 335V | 335V | 580V |
TOV 120 min | 230V | 440V | 440V | 440V | 765V |
modus | Tåler | Sikker feil | Sikker feil | Sikker feil | Sikker feil |
Mekaniske og miljømessige spesifikasjoner
- Driftstemperaturområde: -40 °F til +158 °F [-40 °C til +70 °C].
- Tillatt luftfuktighet ved drift: 5%...95%
- Atmosfærisk trykk og høyde: 80k Pa ... 106k Pa / -500 m....2000 m
- Dreiemoment for terminalskruer: 39,9 lbf.in [4,5 Nm]
- Ledertverrsnitt (maks.): 2 AWG (massiv, fåtrådet) / 4 AWG (fleksibel)
- 35 mm² (massiv, flertrådet) / 25 mm² (fleksibel)
- Montering: 35 mm DIN-skinne, EN 60715
- Grad av beskyttelse: IP 20 (innebygd)
- Materiale i huset: Termoplast: Slukningsgrad UL 94 V-0
- Termisk beskyttelse: Ja
- Driftstilstand / feilindikering: Grønn ok / Rød defekt
Ytterligere funksjoner
- Fjernkontakter (RC): Valgfritt
- RC Switching Capacity: VEKSELSTRØM: 250V / 0,5 A; LIKESTRØM: 250V / 0,1 A;125V / 0,2 A;75V / 0,5 A
- Tverrsnitt for RC-leder (maks.): 16 AWG (Solid) / 1,5 mm² (Solid)