VIOX VRO6-63 4P Elektroniskais tips 6-63A RCBO

VIOX VRO6-63 4P RCBO offers advanced protection for three-phase systems. This IEC61009-1 compliant device features 6kA or 10kA breaking capacity and supports currents from 6A to 63A at 415V AC. With adjustable sensitivity (30mA, 100mA, 300mA), it provides comprehensive A/AC type protection against residual currents, short circuits, and overloads. The RCBO offers B, C, and D tripping curves, IP20 protection, and operates from -25°C to +40°C. Key advantages include fault current indication, versatile terminal connections, and 20,000 operation lifespan. Suitable for industrial and commercial applications, this electronic RCBO ensures reliable protection with clear overload/residual current characteristics and easy DIN rail mounting.

Nosūtiet savas prasības, un mēs piedāvāsim jums cenu 12 stundu laikā.

VIOX VRO6-63 4P Elektroniskais 6-63A tipa atlikušās strāvas slēdžs ar pārslodzes aizsardzību

Pārskats

The VIOX VRO6-63 is a versatile 4-pole Residual Current Circuit Breaker with Overcurrent protection (RCBO) designed for comprehensive electrical protection. This electronic type RCBO offers a wide range of current ratings and advanced safety features, making it suitable for various industrial and commercial applications.

Galvenās funkcijas

  • Standard: IEC61009-1, GB16917.1
  • Mode: Electronic
  • Type: A/AC
  • Klupšanas līkne: B, C, D
  • Pole No.: 4P
  • Rated voltage: 415V~
  • Nominālā frekvence: 50/60 Hz
  • Rated current: 6-63A
  • Rated residual operating current (I△n): 30, 100, 300mA
  • Residual operating current range: 0.5I△n~I△n
  • Rated breaking capacity (Icn): 6000A, 10000A
  • Energy limiting class: 3
  • Electrical and Mechanical life: 20,000 operations

Tehniskās specifikācijas

  • Fault current indicator: YES
  • Aizsardzības pakāpe: AIZSARDZĪBAS PAKĀPE: IP20
  • Ambient temperature: -25°C to +40°C (24h average not exceeding +35°C)
  • Storage temperature: -25°C to +70°C
  • Terminal connection type: Cable/U-type busbar/Pin-type busbar
  • Terminal size top for cable: 25mm²
  • Tightening torque: 2.5N.m
  • Montāža: Uz DIN sliedes EN 60715 (35 mm) ar ātrās fiksācijas ierīci.
  • Connection: Top and bottom

Pārslodzes strāvas aizsardzības raksturlielumi

Test procedure Tips Testa strāva Sākotnējais stāvoklis Tripping or Non-tripping Time Limit Expected Result Piezīme
a B,C,D 1.13In cold t≤1h no tripping
b B,C,D 1.45In after test a t<1h tripping The current steadily rises to the specified value within 5s
c B,C,D 2.55In cold 1s<t<60s tripping
d B
C
D
3In
5In
10In
cold t≤0,1s no tripping Turn on the auxiliary switch to close the current
e B
C
D
5In
10In
20In
cold t<0.1s tripping Turn on the auxiliary switch to close the current

Residual Current Operating Breaking Time

Tips In/A I△n/A Residual Current (I△) Is Corresponding To The Following Breaking Time (S)
AC Type any
value
any
value
1ln 2In 5In 5A,10A,20A,50A
100A,200A,500A
A Type >0.01 1.4In 2.8In 7In
0.3 0.15 0.04 Maksimālais pārtraukuma laiks
The general type RCBO whose current IΔn is 0.03mA or less can use 0.25A instead of 5IΔn.

Saistītie produkti

Pieprasīt citātu tagad

Pieprasīt citātu tagad