VIOX VMM3-400 3P 400A MCCB

VIOX VMM3-400 3P 400A MCCB: High-performance circuit breaker for power distribution networks. Features 3-pole design with 400A rated current. Operates at 400V/690V AC with 800V rated insulation voltage. Available in standard (S) and higher (H) breaking capacity types. Compliant with IEC60947-2 and GB/T14048.2 standards. Offers inverse time breaking action and adjustable instantaneous trip settings. Suitable for altitudes up to 2000m and temperatures from -5°C to +40°C. Multiple N-pole configurations available for four-pole products. Compact design with comprehensive model coding system for precise specifications. Ideal for industrial and commercial applications requiring reliable short-circuit protection and versatile installation options in demanding electrical environments.

Надішліть свої вимоги, і ми надамо вам пропозицію протягом 12 годин

VIOX VMM3-400 3P 400A Moulded Case Circuit Breaker (MCCB)

Огляд продукту

The Viox VMM3-400 is a high-performance 3-pole 400A Moulded Case Circuit Breaker designed for short-circuit protection in power distribution networks. With its compact size, high breaking capacity, and versatile features, it’s an ideal solution for various industrial and commercial applications.

Ключові особливості

  • Rated Current: Up to 400A
  • Poles: Available in 2P, 3P, 4P configurations
  • Rated Working Voltage: 400V/690V AC
  • Rated Insulation Voltage: 800V
  • Breaking Capacity: Standard (S) and Higher (H) types available
  • Compliance: IEC60947-2 and GB/T14048.2 standards

Технічні характеристики

Circuit breaker rating

Модель Frame rating
rated current
In(mA)
Rated
current
In(A)
Rated
working
voltage (V)
Rated
Insulation
voltage (V)
Rated ultimate
short circuit
breaking
capacity Icu(kA)
Rated operating
short-circuit
breaking
capacity Ics(kA)
Number
of
poles
Flashover
distance
(mm)
VMM3-125S 125 16,20,25,32,
40,50,60,80,
100,125
400/415 1000 25 18 3P ≤50
VMM3-125H 125 35 25 3P
VMM3-250S 250 100,125,160,
180,200,225,
250
400/690 800 35/10 25/5 2P,3P,4P ≤50
VMM3-250S 250 600 50 35

 

Inverse time breaking action characteristics of overcurrent release of distribution circuit breaker when all poles are energized at the same time

Test current name I/In Appointed time Starting state
Agreed no tripping current 1.05 2h(In>63A),1h(In≤63A) Cold state
Agreed tripping current 1.3 2h(In>63A),1h(In≤63A) Immediately after the sequence 1 test, start

 

Inverse time breaking action characteristics of overcurrent release of circuit breaker for motor protection when all poles are energized at the same time

Setting current Appointed time Starting state Remark
1.0In >2h Cold state
1.2In ≤2h Immediately after the sequence 1 test, start
1.5In ≤4min cold state 10 ≤ In ≤ 250
≤8min cold state 250 ≤ In ≤ 630
7.2In 4s≤T≤10s cold state 10 ≤ In ≤ 250
6s≤T≤20s cold state 250 ≤ In ≤ 800

The instantaneous operating characteristics of the circuit breaker for distribution are set to 10In±20%, and the instantaneous operating characteristics of the circuit breaker for motor protection are set to 12In±20%.

Operating Conditions

  • Altitude: Not exceeding 2000m
  • Ambient Temperature: -5°C to +40°C (24-hour average not exceeding +35°C)
  • Relative Humidity: Not exceeding 50% at +40°C, higher humidity allowed at lower temperatures
  • Pollution Level: 3

N-pole Types

Four types of neutral pole (N pole) configurations are available for four-pole products:

  • A-type N pole: Not equipped with overcurrent tripping components, always connected
  • B-type N pole: Equipped with overcurrent tripping component, N pole is closed first and opened together with other poles
  • C-type N pole: Equipped with an overcurrent tripping component, N pole is closed and opened together with other poles
  • D-type N pole: Equipped with an overcurrent tripping component, always connected

Product Model Coding System

The VMM3 series uses a comprehensive coding system to specify exact configurations:

  • V: Company code (Viox)
  • M: Moulded case circuit breaker
  • M3: Design code
  • -: Separator
  • □: Breaking capacity characteristic code (S for standard type, H for higher type)
  • □: Frame rating/rated current
  • /: Separator
  • □: Number of poles (2P, 3P, 4P)
  • □: Trip mode (2 for single magnetic, 3 for thermal magnetic)
  • □: Release code (see Table 1 for details)
  • □: Purpose code (2 for protecting power distribution)
  • □: N-pole type (see note for details)

Release Options (Table 1)

Attachment code Electromagnetic release Duplex release
No accessories 200 300
Alarm contact 208 308
Shunt tripper 210 310
Auxiliary contacts 220 320

Shape Size and Installation Dimensions

CJMM3-125, 250 appearance and installation dimensions (Front panel wiring)
Модель Розміри Installation dimensions
L W H L1 L2 W1 W2 W3 H1 H2 H3 H4 C E F G G1 A B Φd
VMM3-125S 150 92 76 251 132 30 95.5 26 18 3 95 49 28 17.5 8 30 129 4
VMM3-125H 150 92 76 251 132 30 95.5 26 18 3 95 49 28 17.5 8 30 129 4
VMM3-250S 165 106 87 300 144 35 75 110 24 20 3 102 57 24.5 23.5 11.5 35 126 5.5
VMM3-250H 165 106 105 300 144 35 142 75 127 24 20 3 102 57 24.5 23.5 11.5 35 126 5.5

The Viox VMM3-400 3P 400A MCCB offers reliable circuit protection with its robust design and advanced features. It’s an excellent choice for demanding electrical environments where performance and safety are paramount.

Супутні товари

Запитайте пропозицію зараз

Запитайте пропозицію зараз