VIOX VSP1-D20/1(S)+1 Pluggbar enpolig SPD
VIOX VSP1-D20/1(S)+1 Pluggable Single-Pole SPD offers comprehensive surge protection for sub-distribution boards. This Class II+III/Type 2+3 device safeguards L-N and N-PE modes with 10kA nominal and 20kA maximum discharge current. Featuring high-energy MOV and GDT elements, it operates from 60V to 400V AC with <25ns response time for L-N and <100ns for N-PE. IEC 61643-11:2011 and EN 61643-11:2012 compliant, it provides voltage protection levels from 0.2kV to 1.8kV. With IP20 protection, thermal safeguards, and optional remote contacts, this versatile SPD suits various electrical installations, combining reliability and performance for enhanced power system protection in diverse applications.
Skicka dina krav, vi kommer att offerera för dig inom 12 timmar
- TEL:+8618066396588
- Whatsapp:+8618066396588
- Email:sales@viox.com
VIOX VSP1-D20/1(S)+1 Pluggbar enpolig SPD
Översikt
The VIOX VSP1-D20/1(S)+1 is a high-performance Pluggable Single-Pole Surge Protective Device (SPD) designed for use in sub-distribution boards. This versatile device offers robust protection for L-N and N-PE modes, making it an ideal solution for various electrical installations.
Viktiga funktioner
- Klass II, Klass III, Typ 2, Typ 3 enhet
- Plats för användning: Underdistributionscentraler
- Mode of Protection: L-N, N-PE
- Klassning för överspänning: Ingång = 10 kA (8/20 μs)
- IEC/EN/UL Kategori: Klass II+III / Typ 2+3
- Protective Elements: High Energy MOV and GDT
- Hölje: Pluggbar design
- Överensstämmelse: IEC 61643-11:2011, EN 61643-11:2012
Tekniska specifikationer
IEC Elektrisk | 75 | 150 | 275 | 320 | 385 | 440 |
---|---|---|---|---|---|---|
Nominell AC-spänning (50/60Hz) | 60 V | 120 V | 230 V | 230 V | 230 V | 400 V |
Maximum Continuous Operating Voltage (AC) (L-N) | 75 V | 150 V | 275V | 320 V | 385 V | 440 V |
Maximum Continuous Operating Voltage (AC) (N-PE) | 255V | |||||
Nominal Discharge Current (8/20 μs) (L-N) / (N-PE) | 10kV / 10kA | |||||
Maximum Discharge Current (8/20 μs) (L-N) / (N-PE) | 20 kA / 20 kA | |||||
Voltage Protection Level (L-N) / (N-PE) | 0.2kV/1.5kV | 0.6kV/1.5kV | 1.3kV/1.5kV | 1.5kV/1.5kV | 1.5kV/1.5kV | 1.8kV/1.5kV |
Follow Current Interrupt Rating (N-PE) | 100Arms | |||||
Response Time (L-N) / (N-PE) | < 25 ns / < 100 ns | |||||
Reservsäkring (max) | 125 A gL / gG | |||||
Short-Circuit Current Rating (AC) (L-N) | 10 kA | |||||
TOV Withstand 5s (L-N) | 90V | 180V | 335V | 335V | 335V | 580V |
TOV 120min (L-N) | 115V | 230V | 440V | 440V | 440V | 765V |
läge | Motstånd | Motstånd | Säkert fel | Säkert fel | Säkert fel | Säkert fel |
TOV Withstand 200ms (N-PE) | 1200V |
Mekaniska och miljömässiga specifikationer
- Driftstemperaturområde: -40°F till +158°F [-40°C till +70°C].
- Tillåten luftfuktighet vid drift: 5%...95%
- Atmosfäriskt tryck och höjd: 80k Pa ... 106k Pa / -500 m....2000 m
- Vridmoment för terminalskruv: 39,9 lbf.in [4,5 Nm]
- Ledarens tvärsnitt (max): 2 AWG (solid, fåtrådig) / 4 AWG (flexibel)
- 35 mm² (solid, fåtrådig) / 25 mm² (flexibel)
- Montering: 35 mm DIN-skena, EN 60715
- Grad av skydd: IP 20 (inbyggd)
- Material i höljet: Termoplast: Släckningsgrad UL 94 V-0
- Termiskt skydd: Ja
- Drifttillstånd / felindikering: Grön ok / Röd defekt
Ytterligare funktioner
- Fjärrkontakter (RC): Tillval
- RC Switching Capacity: AC: 250V / 0.5 A; DC: 250V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
- RC-ledarens tvärsnitt (max): 16 AWG (Solid) / 1,5 mm² (Solid)