VIOX VSP1-D20/4(S) Pluggbar flerpolet SPD
VIOX VSP1-D20/4(S) Pluggable Multi-Pole SPD offers comprehensive surge protection for sub-distribution boards. This Class II+III/Type 2+3 device safeguards L-PE and N-PE modes with 10kA nominal and 20kA maximum discharge current. Featuring high-energy MOV elements, it operates from 120V to 400V AC with < 25ns response time. The pluggable design ensures easy installation on 35mm DIN rails. IEC 61643-11:2011 and EN 61643-11:2012 compliant, it provides voltage protection levels from 0.6kV to 1.8kV. With IP20 protection, thermal safeguards, and optional remote contacts, this versatile SPD suits various electrical installations, combining reliability and performance in a compact, user-friendly package for enhanced multi-pole power system protection in diverse applications.
Send oss dine krav, så gir vi deg et tilbud innen 12 timer
- TEL:+8618066396588
- Whatsapp:+8618066396588
- Email:sales@viox.com
VIOX VSP1-D20/4(S) Pluggbar flerpolet SPD
Oversikt
VIOX VSP1-D20/4(S) er en høytytende pluggbar flerpolet overspenningsvern (SPD) designet for bruk i underfordelingsskap. Denne allsidige enheten tilbyr robust beskyttelse for både L-PE- og N-PE-modus, noe som gjør den til en ideell løsning for ulike elektriske installasjoner.
Viktige funksjoner
- Klasse II, klasse III, type 2, type 3-enhet
- Bruksområde: Underdistribusjonstavler
- Beskyttelsesmodus: L-PE, N-PE
- Overspenningsverdier: In = 10 kA (8/20 μs)
- IEC/EN/UL Kategori: Klasse II+III / Type 2+3
- Beskyttelseselementer: Høyenergi MOV
- Hus: Pluggbar design
- Samsvar: IEC 61643-11:2011, EN 61643-11:2012
Tekniske spesifikasjoner
IEC Elektrisk | 150 | 275 | 320 | 385 | 440 |
---|---|---|---|---|---|
Nominell vekselstrømspenning (50/60 Hz) | 120 V | 230 V | 230 V | 230 V | 400 V |
Maksimal kontinuerlig driftsspenning (AC) | 150 V | 275V | 320 V | 385 V | 440 V |
Nominell utladningsstrøm (8/20 μs) | 10 kA | 10 kA | 10 kA | 10 kA | 10 kA |
Maksimal utladningsstrøm (8/20 μs) | 20 kA | 20 kA | 20 kA | 20 kA | 20 kA |
Spenningsbeskyttelsesnivå | 0,6 kV | 1,3 kV | 1,5 kV | 1,5 kV | 1,8 kV |
Responstid | < 25 ns | ||||
Reservesikring (maks.) | 125 A gL / gG | ||||
Kortslutningsstrøm (AC) | 10 kA | ||||
TOV Tåler 5s | 180V | 335V | 335V | 335V | 580V |
TOV 120 min | 230V | 440V | 440V | 440V | 765V |
modus | Tåler | Sikker feil | Sikker feil | Sikker feil | Sikker feil |
Mekaniske og miljømessige spesifikasjoner
- Driftstemperaturområde: -40 °F til +158 °F [-40 °C til +70 °C].
- Tillatt luftfuktighet ved drift: 5%...95%
- Atmosfærisk trykk og høyde: 80k Pa ... 106k Pa / -500 m....2000 m
- Dreiemoment for terminalskruer: 39,9 lbf.in [4,5 Nm]
- Ledertverrsnitt (maks.): 2 AWG (massiv, fåtrådet) / 4 AWG (fleksibel)
- 35 mm² (massiv, flertrådet) / 25 mm² (fleksibel)
- Montering: 35 mm DIN-skinne, EN 60715
- Grad av beskyttelse: IP 20 (innebygd)
- Materiale i huset: Termoplast: Slukningsgrad UL 94 V-0
- Termisk beskyttelse: Ja
- Driftstilstand / feilindikering: Grønn ok / Rød defekt
Ytterligere funksjoner
- Fjernkontakter (RC): Valgfritt
- RC Switching Capacity: VEKSELSTRØM: 250V / 0,5 A; LIKESTRØM: 250V / 0,1 A;125V / 0,2 A;75V / 0,5 A
- Tverrsnitt for RC-leder (maks.): 16 AWG (Solid) / 1,5 mm² (Solid)