VIOX VRO3-40 1P+N RCBO

VIOX VRO3-40 RCBO offers comprehensive protection for single-phase systems. This IEC61009-1 compliant device features a 6kA breaking capacity and supports currents from 6A to 40A at 230V AC. With adjustable sensitivity from 10mA to 500mA, it provides A and AC type protection against residual currents, overloads, and short circuits. The RCBO offers B, C, and D tripping curves, IP20 protection, and operates from -5°C to +40°C. Key advantages include combined MCB/RCD functionality, 1P+N configuration, and 4,000 electrical/10,000 mechanical life cycles. Ideal for residential and commercial applications, this versatile RCBO ensures reliable protection with fault current indication, 4kV impulse withstand voltage, and easy DIN rail mounting. Its compact design and top connection make it suitable for various low-voltage distribution systems.

Atsiųskite savo reikalavimus, mes pateiksime jums pasiūlymą per 12 valandų

VIOX VRO3-40 1P+N RCBO ELCB liekamosios srovės grandinės pertraukiklis su apsauga nuo viršįtampių

Apžvalga

The VIOX VRO3-40 is a versatile Residual Current Circuit Breaker with Overcurrent Protection (RCBO) designed for AC 50Hz/60Hz systems with rated voltage 230/400V and rated current from 6A to 40A. This device combines the functions of an MCB and RCD, offering comprehensive protection against electric shock, overload, and short circuits in low voltage terminal distribution systems.

Pagrindinės funkcijos

  • Combined MCB and RCD functionality
  • Protection against electric shock and indirect human contact
  • Overload and short circuit protection
  • Suitable for non-frequent circuit operation
  • Widely used in residential and commercial applications
  • Atitinka IEC61009-1 standartą

Techninės specifikacijos

  • Standard: IEC/EN 61009-1
  • Mode: Electro-magnetic type, electronic type
  • Type: A, AC (wave form of earth leakage sensed)
  • Thermo-magnetic release characteristic: B, C, D
  • Rated current (In): 6, 10, 16, 20, 25, 32, 40A
  • Poles: 1P+N
  • Rated voltage (Ue): AC 230V
  • Rated sensitivity (I△n): 0.01, 0.03, 0.1, 0.3, 0.5A
  • Rated residual making and breaking capacity (I△m): 500A
  • Rated short-circuit capacity (Icn): 6000A
  • Break time under I△n: ≤0.1s
  • Nominalusis dažnis: 50/60 Hz
  • Rated impulse withstand voltage (Uimp): 4000V
  • Dielectric test voltage: 2kV for 1 min
  • Insulation voltage (Ui): 250V
  • Užterštumo laipsnis: 2

Mechaninės savybės

  • Electrical life: 4000 operations
  • Mechanical life: 10000 operations
  • Fault current indicator: Yes
  • Apsaugos laipsnis: IP20
  • Ambient temperature: -5~+40°C (daily average ≤35°C)
  • Storage temperature: -25~+70°C

Įrengimas

  • Terminal connection type: Cable/Pin-type busbar/U-type busbar
  • Terminal size for cable: 25mm² (AWG 18-5)
  • Terminal size for busbar: 25mm² (AWG 18-3)
  • Montavimas: Ant DIN bėgio EN 60715 (35 mm), naudojant greito fiksavimo įtaisą
  • Connection: From top

Paraiškos

  • Gyvenamųjų namų elektros sistemos
  • Komerciniai pastatai
  • Low voltage terminal distribution systems

Saugos funkcijos

  • Electric shock protection
  • Apsauga nuo perkrovos
  • Apsauga nuo trumpojo jungimo
  • Leakage current detection

Charakteristinė kreivė

Elektros instaliacijos schema

Matmenys

Susiję produktai

Paklauskite citatos dabar

Paklauskite citatos dabar