VIOX VSP1-C40/3(S) ühendatav mitmepooluseline SPD
VIOX VSP1-C40/3(S) Pluggable Multi-Pole SPD offers robust surge protection for sub-distribution boards. This Class II/Type 2/Type 1CA device safeguards L-PE and N-PE modes with 20kA nominal and 40kA maximum discharge current. Featuring high-energy MOV elements, it operates from 120V to 400V AC with < 25ns response time. The pluggable design ensures easy installation on 35mm DIN rails. IEC 61643-11:2011 and EN 61643-11:2012 compliant, it provides voltage protection levels from 1kV to 2kV. With IP20 protection, thermal safeguards, and optional remote contacts, this versatile SPD suits various electrical installations, combining reliability and performance in a compact, user-friendly package for enhanced multi-pole power system protection in demanding applications.
Saatke oma nõuded, me teeme teile hinnapakkumise 12 tunni jooksul.
- TEL:+8618066396588
- Whatsapp:+8618066396588
- Email:sales@viox.com
VIOX VSP1-C40/3(S) ühendatav mitmepooluseline SPD
Ülevaade
The VIOX VSP1-C40/3(S) is a high-performance Pluggable Multi-Pole Surge Protective Device (SPD) designed for use in sub-distribution boards. This versatile device offers robust protection for L-PE and N-PE modes, making it an ideal solution for various electrical installations.
Peamised omadused
- II klassi, 2. tüübi, 1CA tüüpi seade
- Kasutamise koht: alajaotuskilbid
- Kaitserežiim: L-PE, N-PE
- Hinnangu tõus: In = 20 kA (8/20 μs)
- IEC/EN/UL Kategooria: Klass II / tüüp 2 / tüüp 1CA
- Kaitseelemendid: MOV
- Eluase: Ühendatav disain
- Vastavus: 61643-11:2011, EN 61643-11:2012.
Tehnilised andmed
IEC Elektriline | 150 | 275 | 320 | 385 | 440 |
---|---|---|---|---|---|
Nimivoolupinge (50/60 Hz) | 120 V | 230 V | 230 V | 230 V | 400 V |
Maksimaalne pidev tööpinge (vahelduvvool) | 150 V | 275V | 320 V | 385 V | 440 V |
Nominaalne tühjendusvool (8/20 μs) | 20 kA | 20 kA | 20 kA | 20 kA | 20 kA |
Maksimaalne tühjendusvool (8/20 μs) | 40 kA | 40 kA | 40 kA | 40 kA | 40 kA |
Pinge kaitse tase | 1 kV | 1,5 kV | 1,6 kV | 1,8 kV | 2 kV |
Impulssvool (10/350μs) Iimp (L-N) | 7kA | ||||
Reageerimisaeg | < 25 ns | ||||
Tagavaraturvasulavkaitse (max) | 125 A gL / gG | ||||
Lühisvoolu nimiväärtus (vahelduvvool) | 25 kA / 50 kA | ||||
TOV Vastupidavus 5s | 180V | 335V | 335V | 335V | 580V |
TOV 120min | 230V | 440V | 440V | 440V | 765V |
režiim | Vastupidavus | Ohutu ebaõnnestumine | Ohutu ebaõnnestumine | Ohutu ebaõnnestumine | Ohutu ebaõnnestumine |
Mehaanilised ja keskkonnaalased spetsifikatsioonid
- Töötemperatuurivahemik: -40°F kuni +158°F [-40°C kuni +70°C]
- Lubatud tööniiskus: 5%...95%
- Atmosfäärirõhk ja kõrgus: 80k Pa ... 106k Pa / -500 m....2000 m
- Klemmikruvi pöördemoment: 39,9 lbf.in [4,5 Nm].
- Juhtme ristlõige (max): 4 AWG (paindlik) / 2 AWG (täismass, mitmekordne)
- 35 mm² (tahke, mitmekihiline) / 25 mm² (paindlik)
- Paigaldamine: 35 mm DIN rööbas, EN 60715
- Kaitseaste: IP 20 (sisseehitatud)
- Korpuse materjal: UL 94 V-0.
- Termiline kaitse: Jah
- Tööseisund / veamärguanne: Roheline ok / Punane defekt
Täiendavad omadused
- Kaugkontaktid (RC): Valikuline
- RC lülitusvõimsus: AC: 250V / 0,5 A; DC: 250V / 0,1 A; 125V / 0,2 A; 75V / 0,5 A
- RC-juhi ristlõige (max): 1,5 mm² (tahke) / 16 AWG (tahke)